Rapid Building Performance Assessment of Administrative Office Complex, Kigali, Rwanda

Report an error

Summary

AI-generated

This summary is written by a language model reading the source document. It is not the publisher's words and is not a substitute for the original.

Learn more about AI enrichment

The assessment of the Administrative Office Complex in Kigali finds that while the building has a relatively low Energy Performance Index of 36 kWh/m2/year, there are significant opportunities to reduce GHG emissions and operational costs through LED lighting upgrades and restored rainwater harvesting.

Key insights

AI-generated

These insights are written by a language model reading the source document. They are not the publisher's words and are not a substitute for the original.

Learn more about AI enrichment
  • The Administrative Office Complex (AOC) has an Energy Performance Index (EPI) of approximately 36 kWh/m2/year and a Water Efficiency Index (WEI) of approximately 0.47 m3/m2/year, both of which are considered low when compared to benchmarks in India and Singapore.
  • The building's orientation along the North-West and South-East axis is suboptimal for its location in Kigali, leading to excessive heat gain, particularly on the western façade, which is further exacerbated by a high Window to Wall Ratio (WWR) in the central wing.
  • Approximately 70% of the indoor lighting consists of non-LED fixtures, specifically 18W Fluorescent T8 Tube lights in office spaces, which presents a significant opportunity for energy savings through replacement.
  • The building's air-conditioning system uses R-410A refrigerant, which has a high Global Warming Potential (GWP) of 2088 and should be phased out in accordance with the Kigali amendment to the Montreal Protocol.
  • The rainwater harvesting system, designed to hold approximately 360 cubic meters of water, is currently non-functional because the pump room was submerged during heavy rains in January 2020, damaging the pumping equipment.
  • The wastewater treatment system is inadequate because the grey water tank was constructed as a non-permeable RCC tank rather than a soak pit, causing it to fill quickly and requiring frequent emptying.
  • Annual indirect GHG emissions from grid-supplied electricity for the AOC are estimated at 170.5 tCO2e, based on consumption data from October 2019 to September 2020.

Cite the original document

APA
Global Green Growth Institute (2021). Rapid Building Performance Assessment of Administrative Office Complex, Kigali, Rwanda. https://gggi.org/wp-content/uploads/2021/06/AOC-Report_low-res_Final.pdf
Chicago
Global Green Growth Institute. Rapid Building Performance Assessment of Administrative Office Complex, Kigali, Rwanda. 2021. https://gggi.org/wp-content/uploads/2021/06/AOC-Report_low-res_Final.pdf.
Wikipedia
{{cite report |author=Global Green Growth Institute |title=Rapid Building Performance Assessment of Administrative Office Complex, Kigali, Rwanda |date=March 2021 |url=https://gggi.org/wp-content/uploads/2021/06/AOC-Report_low-res_Final.pdf |access-date=5 November 2026 |via=Climate Insights Directory (document gggi-000218)}}
BibTeX
@techreport{globalgreengrowthinstitute2021rapid, author = {{Global Green Growth Institute}}, title = {{Rapid Building Performance Assessment of Administrative Office Complex, Kigali, Rwanda}}, institution = {Global Green Growth Institute}, year = {2021}, month = mar, url = {https://gggi.org/wp-content/uploads/2021/06/AOC-Report_low-res_Final.pdf}, urldate = {2026-11-05}, note = {Indexed by Climate Insights Directory, document gggi-000218} }

Full text

Collected · Record updated